| 20000 |
RO |
The type of machine High |
PH/EP/PV |
| 20001 |
RO |
The type of machine Low |
1800/3000 |
| 20002 |
RW |
Serial number High |
|
| 20003 |
RW |
Serial number Low |
|
| 20004 |
RO |
Hardware version |
1.00.00 |
| 20005 |
RO |
Software version |
1.00.00 |
| 20006 |
RO |
Communication Protocal Edition |
1.00.00 |
| 20009 |
RW |
Battery voltage calibration coefficient |
16384 |
| 20010 |
RW |
Inverter voltage calibration coefficient |
16384 |
| 20011 |
RW |
Grid voltage calibration coefficient |
16384 |
| 20012 |
RW |
Bus voltage calibration coefficient |
16384 |
| 20013 |
RW |
Control Current calibration coefficient |
16384 |
| 20014 |
RW |
Inverter Current calibration coefficient |
16384 |
| 20015 |
RW |
Grid Current calibration coefficient |
16384 |
| 20016 |
RW |
Load Current calibration coefficient |
16384 |
| 20101 |
RW |
Inverter offgrid work enable |
0:OFF 1:ON |
| 20102 |
RW |
Inverter output voltage Set |
220.0V-240.0V |
| 20103 |
RW |
Inverter output frequency Set |
50.00Hz/60.00Hz |
| 20104 |
RW |
Inverter search mode enable |
0:OFF 1:ON |
| 20108 |
RW |
Inverter discharger to grid enable |
48V: 0:OFF 1:ON 24V: Null |
| 20109 |
RW |
Energy use mode |
48V:1:SBU;2:SUB;3:UTI;4:SOL (for PV;PH) 1:BAU; 3:UTI;4:BOU (for EP) 12V 24V:1:SBU;;3:UTI;4:SOL (for PV;PH) 1:BU; 3:UTI (for EP) |
| 20111 |
RW |
Grid protect standard |
0:VDE4105; 1:UPS ; 2:home ;3:GEN |
| 20112 |
RW |
SolarUse Aim |
0:LBU 1:BLU(defalut)(for PV;PH) 0:LB 1:LU(defalut) (for EP) |
| 20113 |
RW |
Inverter max discharger current |
48V: 0.1A(AC) 12V 24V: Null |
| 20118 |
RW |
Battery stop discharging voltage |
0.1V |
| 20119 |
RW |
Battery stop charging voltage |
0.1V |
| 20125 |
RW |
Grid max charger current set |
0.1A(DC) |
| 20127 |
RW |
Battery low voltage |
0.1V |
| 20128 |
RW |
Battery high voltage |
0.1V |
| 20132 |
RW |
Max Combine charger current |
0.1A(DC)(for PV;PH) |
| 20142 |
RW |
System setting |
|
| 20143 |
RW |
Charger source priority |
0:Soalr first (for PV;PH) 2:Solar and Utility(default) (for PV;PH) 3:Only Solar (for PV;PH) 2:Utility charger enable (default) (for EP) 3:Utility charger disable (for EP) |
| 20144 |
RW |
Solar power balance |
0:SBD 1:SBE |
| 20213 |
RW |
Remove the accumulated data |
0:No remove the accumulated data 1:Remove the accumulated data |
| 20214 |
RW |
Reset the parameter |
0:No effect 1:Action |
| 25201 |
RO |
work state |
0:PowerOn 1:SelfTest 2:OffGrid 3:Grid-Tie 4:ByPass 5:Stop 6:Grid charging |
| 25202 |
RO |
AC voltage grade |
230:230V 120:120V |
| 25203 |
RO |
Rated power(VA) |
VA |
| 25204 |
RO |
reserved |
|
| 25205 |
RO |
Battery voltage |
0.1V |
| 25206 |
RO |
Inverter voltage |
0.1V |
| 25207 |
RO |
Grid voltage |
0.1V |
| 25208 |
RO |
BUS voltage |
0.1V |
| 25209 |
RO |
Control current |
0.1A |
| 25210 |
RO |
Inverter current |
0.1A |
| 25211 |
RO |
Grid current |
0.1A |
| 25212 |
RO |
Load current |
0.1A |
| 25213 |
RO |
PInverter |
1W |
| 25214 |
RO |
PGrid |
1W |
| 25215 |
RO |
PLoad |
1W |
| 25216 |
RO |
Load percent |
0.01 |
| 25217 |
RO |
SInverter |
1VA |
| 25218 |
RO |
SGrid |
1VA |
| 25219 |
RO |
Sload |
1VA |
| 25220 |
RO |
reserved |
|
| 25221 |
RO |
Qinverter |
1var |
| 25222 |
RO |
Qgrid |
1var |
| 25223 |
RO |
Qload |
1var |
| 25224 |
RO |
reserved |
|
| 25225 |
RO |
Inverter frequency |
0.01Hz |
| 25226 |
RO |
Grid frequency |
0.01Hz |
| 25227 |
RO |
reserved |
|
| 25228 |
RO |
reserved |
|
| 25229 |
RO |
Inverter max number |
|
| 25230 |
RO |
Combine type |
|
| 25231 |
RO |
Inverter number |
|
| 25232 |
RO |
reserved |
|
| 25233 |
RO |
AC radiator temperature |
1℃ |
| 25234 |
RO |
Transformer temperature |
1℃ |
| 25235 |
RO |
DC radiator temperature |
1℃ |
| 25236 |
RO |
reserved |
|
| 25237 |
RO |
Inverter relay state |
0: Disconnect 1:Connect |
| 25238 |
RO |
Grid relay state |
0: Disconnect 1:Connect |
| 25239 |
RO |
Load relay state |
0: Disconnect 1:Connect |
| 25240 |
RO |
N_Line relay state |
0: Disconnect 1:Connect |
| 25241 |
RO |
DC relay state |
0: Disconnect 1:Connect |
| 25242 |
RO |
Earth relay state |
0: Disconnect 1:Connect |
| 25243 |
RO |
reserved |
|
| 25244 |
RO |
reserved |
|
| 25245 |
RO |
Accumulated charger power high |
1000KWH |
| 25246 |
RO |
Accumulated charger power low |
0.1KWH |
| 25247 |
RO |
Accumulated discharger power high |
1000KWH |
| 25248 |
RO |
Accumulated discharger power low |
0.1KWH |
| 25249 |
RO |
Accumulated buy power high |
1000KWH |
| 25250 |
RO |
Accumulated buy power low |
0.1KWH |
| 25251 |
RO |
Accumulated sell power high |
1000KWH |
| 25252 |
RO |
Accumulated sell power low |
0.1KWH |
| 25253 |
RO |
Accumulated load power high |
1000KWH |
| 25254 |
RO |
Accumulated load power low |
0.1KWH |
| 25255 |
RO |
Accumulated self_use power high |
1000KWH |
| 25256 |
RO |
Accumulated self_use power low |
0.1KWH |
| 25257 |
RO |
Accumulated PV_sell power high |
1000KWH |
| 25258 |
RO |
Accumulated PV_sell power low |
0.1KWH |
| 25259 |
RO |
Accumulated grid_charger power high |
1000KWH |
| 25260 |
RO |
Accumulated grid_charger power low |
0.1KWH |
| 25261 |
RO |
Error message 1 |
|
| 25262 |
RO |
Error message 2 |
|
| 25263 |
RO |
Error message 3 |
|
| 25264 |
RO |
reserved |
|
| 25265 |
RO |
Warning message 1 |
|
| 25266 |
RO |
Warning message 2 |
|
| 25267 |
RO |
reserved |
|
| 25268 |
RO |
reserved |
|
| 25269 |
RO |
Serial number High |
|
| 25270 |
RO |
Serial number Low |
|
| 25271 |
RO |
Hardware version |
1.00.00 |
| 25272 |
RO |
Software version |
1.00.00 |
| 25273 |
RO |
Batt power |
W |
| 25274 |
RO |
Batt current |
A |
| 25275 |
RO |
Batt voltage grade |
48:48V 24:24V 12:12V |
| 25276 |
|
reserved |
|
| 25277 |
RO |
Rated power(W) |
W |
| 25278 |
RO |
Communication Protocal Edition |
1.00.00 |
| 25279 |
RO |
Arrow Flag |
bit |