Sheet: Inverter modbusRTU (ID == 4)

Address Type Name Unit / Values
20000 RO The type of machine High PH/EP/PV
20001 RO The type of machine Low 1800/3000
20002 RW Serial number High
20003 RW Serial number Low
20004 RO Hardware version 1.00.00
20005 RO Software version 1.00.00
20006 RO Communication Protocal Edition 1.00.00
20009 RW Battery voltage calibration coefficient 16384
20010 RW Inverter voltage calibration coefficient 16384
20011 RW Grid voltage calibration coefficient 16384
20012 RW Bus voltage calibration coefficient 16384
20013 RW Control Current calibration coefficient 16384
20014 RW Inverter Current calibration coefficient 16384
20015 RW Grid Current calibration coefficient 16384
20016 RW Load Current calibration coefficient 16384
20101 RW Inverter offgrid work enable 0:OFF 1:ON
20102 RW Inverter output voltage Set 220.0V-240.0V
20103 RW Inverter output frequency Set 50.00Hz/60.00Hz
20104 RW Inverter search mode enable 0:OFF 1:ON
20108 RW Inverter discharger to grid enable 48V: 0:OFF 1:ON 24V: Null
20109 RW Energy use mode 48V:1:SBU;2:SUB;3:UTI;4:SOL (for PV;PH) 1:BAU; 3:UTI;4:BOU (for EP) 12V 24V:1:SBU;;3:UTI;4:SOL (for PV;PH) 1:BU; 3:UTI (for EP)
20111 RW Grid protect standard 0:VDE4105; 1:UPS ; 2:home ;3:GEN
20112 RW SolarUse Aim 0:LBU 1:BLU(defalut)(for PV;PH) 0:LB 1:LU(defalut) (for EP)
20113 RW Inverter max discharger current 48V: 0.1A(AC) 12V 24V: Null
20118 RW Battery stop discharging voltage 0.1V
20119 RW Battery stop charging voltage 0.1V
20125 RW Grid max charger current set 0.1A(DC)
20127 RW Battery low voltage 0.1V
20128 RW Battery high voltage 0.1V
20132 RW Max Combine charger current 0.1A(DC)(for PV;PH)
20142 RW System setting
20143 RW Charger source priority 0:Soalr first (for PV;PH) 2:Solar and Utility(default) (for PV;PH) 3:Only Solar (for PV;PH) 2:Utility charger enable (default) (for EP) 3:Utility charger disable (for EP)
20144 RW Solar power balance 0:SBD 1:SBE
20213 RW Remove the accumulated data 0:No remove the accumulated data 1:Remove the accumulated data
20214 RW Reset the parameter 0:No effect 1:Action
25201 RO work state 0:PowerOn 1:SelfTest 2:OffGrid 3:Grid-Tie 4:ByPass 5:Stop 6:Grid charging
25202 RO AC voltage grade 230:230V 120:120V
25203 RO Rated power(VA) VA
25204 RO reserved
25205 RO Battery voltage 0.1V
25206 RO Inverter voltage 0.1V
25207 RO Grid voltage 0.1V
25208 RO BUS voltage 0.1V
25209 RO Control current 0.1A
25210 RO Inverter current 0.1A
25211 RO Grid current 0.1A
25212 RO Load current 0.1A
25213 RO PInverter 1W
25214 RO PGrid 1W
25215 RO PLoad 1W
25216 RO Load percent 0.01
25217 RO SInverter 1VA
25218 RO SGrid 1VA
25219 RO Sload 1VA
25220 RO reserved
25221 RO Qinverter 1var
25222 RO Qgrid 1var
25223 RO Qload 1var
25224 RO reserved
25225 RO Inverter frequency 0.01Hz
25226 RO Grid frequency 0.01Hz
25227 RO reserved
25228 RO reserved
25229 RO Inverter max number
25230 RO Combine type
25231 RO Inverter number
25232 RO reserved
25233 RO AC radiator temperature 1℃
25234 RO Transformer temperature 1℃
25235 RO DC radiator temperature 1℃
25236 RO reserved
25237 RO Inverter relay state 0: Disconnect 1:Connect
25238 RO Grid relay state 0: Disconnect 1:Connect
25239 RO Load relay state 0: Disconnect 1:Connect
25240 RO N_Line relay state 0: Disconnect 1:Connect
25241 RO DC relay state 0: Disconnect 1:Connect
25242 RO Earth relay state 0: Disconnect 1:Connect
25243 RO reserved
25244 RO reserved
25245 RO Accumulated charger power high 1000KWH
25246 RO Accumulated charger power low 0.1KWH
25247 RO Accumulated discharger power high 1000KWH
25248 RO Accumulated discharger power low 0.1KWH
25249 RO Accumulated buy power high 1000KWH
25250 RO Accumulated buy power low 0.1KWH
25251 RO Accumulated sell power high 1000KWH
25252 RO Accumulated sell power low 0.1KWH
25253 RO Accumulated load power high 1000KWH
25254 RO Accumulated load power low 0.1KWH
25255 RO Accumulated self_use power high 1000KWH
25256 RO Accumulated self_use power low 0.1KWH
25257 RO Accumulated PV_sell power high 1000KWH
25258 RO Accumulated PV_sell power low 0.1KWH
25259 RO Accumulated grid_charger power high 1000KWH
25260 RO Accumulated grid_charger power low 0.1KWH
25261 RO Error message 1
25262 RO Error message 2
25263 RO Error message 3
25264 RO reserved
25265 RO Warning message 1
25266 RO Warning message 2
25267 RO reserved
25268 RO reserved
25269 RO Serial number High
25270 RO Serial number Low
25271 RO Hardware version 1.00.00
25272 RO Software version 1.00.00
25273 RO Batt power W
25274 RO Batt current A
25275 RO Batt voltage grade 48:48V 24:24V 12:12V
25276 reserved
25277 RO Rated power(W) W
25278 RO Communication Protocal Edition 1.00.00
25279 RO Arrow Flag bit

Sheet: Inverter Alarm

Address Type Name Unit / Values

Sheet: PV Charger ModbusRtu (ID == 4)

Address Type Name Unit / Values
10001 RO The type of machine PC1600
10002 WR Serial number High
10003 WR Serial number Low
10004 RO Hardware version 1.0.00
10005 RO Software version 1.0.00
10006 WR PV voltage calibration coefficient 16384
10007 WR Battery voltage calibration coefficient 16384
10008 WR Charger current calibration coefficient 16384
10103 WR Float voltage 0.1V
10104 WR Absorption voltage 0.1V
10105 WR Battery low voltage(for PV;PH) 0.1V
10106 WR reserved
10107 WR Battery High voltage(for PV;PH) 0.1V
10108 WR PV max charger current(for PV;PH) 0.1A
10110 WR Battery type 0:no choose 1:Use defined battery 2:lithium battery 3:SEALED_LEAD battery 4:AGM battery 5:GEL battery 6:FLOODED battery
10111 WR Battery AH 1AH
10112 WR Remove the accumulated data 0:No remove the accumulated data 1:Remove the accumulated data
10118 WR Battery equalization enable 0:Disable 1:Enable
10119 WR Battery Equalization voltage 0.1V
10120 WR reserved reserved
10121 WR Battery equalized time 1min
10122 WR Battery Equalized timeout 1min
10123 WR Equalization interval 1day
10124 WR Equalization actived immediately 0:No effect 1:Action
15201 RO Charger workstate 0:Initialization mode 1:Selftest Mode 2: Work Mode 3:Stop Mode
15202 RO Mppt state 0:Stop 1:MPPT 2: Current limiting
15203 RO charging state 0:Stop 1:Absorb charge 2: Float charge 3:EQ charge
15204 RO reserved
15205 RO PV voltage 0.1V
15206 RO Battery voltage 0.1V
15207 RO Charger current 0.1A
15208 RO Charger power 1W
15209 RO Radiator temperature 1℃
15210 RO External temperature 1℃
15211 RO Battery Relay
15212 RO PV Relay
15213 RO Error message Refer to frame Charger Error message 1
15214 RO Warning message Refer to frame Charger Warning message 1
15215 RO BattVol Grade 1V
15216 RO Rated Current 0.1A
15217 RO Accumulated PV power high 1000KWH
15218 RO Accumulated PV power low 0.1KWH
15219 RO Accumulated day 1day
15220 RO Accumulated hour 1hour
15221 RO Accumulated minute 1minute

Sheet: PV Charger Alarm

Address Type Name Unit / Values