MUST PV1800 register map

Derived from the manufacturer protocol document PH1800 PV1800 EP1800 PV3500 EP3500 RS485 Modbus RTU communication Protocol 1.4.15.xlsx shipped in the taHC81/MUST-ESPhome GitHub repo. Only the registers this monitor reads are listed here; the full document covers hundreds more.

All values are Modbus RTU holding registers (function code 0x03), unless otherwise noted. RO = read-only, RW = read/write.

CHARGER block (start at 15201)

Addr RO/RW Name Unit Notes
15201 RO Charger workstate — 0=Init, 1=Standby, 2=Charging, 3=Fault, 4=Flash
15202 RO MPPT state — 0=Stop, 1=Start, 2=Normal, 3=MPPT limit, 4=Float
15203 RO Charging state — 0=Stop, 1=Precharge, 2=CC, 3=CV, 4=Float, 5=Current derating
15204 RO reserved —
15205 RO PV voltage 0.1 V
15206 RO Battery voltage (charger side) 0.1 V
15207 RO Charger current 0.1 A
15208 RO Charger power W

When you ask for register 15201 with count=1 the inverter dumps the entire block (49 registers, addresses 15201..15249). The registers listed here are 15201..15208.

INVERTER block (start at 25201)

Addr RO/RW Name Unit Notes
25201 RO Work state — 0=PowerOn, 1=SelfTest, 2=OffGrid, 3=GridTie, 4=ByPass, 5=Stop, 6=GridCharging
25202 RO AC voltage grade V 230=230V variant, 120=120V variant
25203 RO Rated power VA
25204 RO reserved
25205 RO Battery voltage 0.1 V
25206 RO Inverter voltage 0.1 V
25207 RO Grid voltage 0.1 V
25208 RO BUS voltage 0.1 V
25209 RO Control current 0.1 A
25210 RO Inverter current 0.1 A
25211 RO Grid current 0.1 A
25212 RO Load current 0.1 A
25213 RO PInverter W signed in this script; protocol says unsigned 1W
25214 RO PGrid W signed (negative = exporting to grid)
25215 RO PLoad W signed (negative = ??? on this firmware)
25216 RO Load percent % unit is percent (raw integer, NOT ×0.01)
25217 RO SInverter VA
... (more S/Q regs, frequencies, temps, relays, accumulators)
25233 RO AC radiator temperature °C
25234 RO Transformer temperature °C
25235 RO DC radiator temperature °C often 0 on units without that sensor
...
25273 RO Batt power W signed
25274 RO Batt current 0.1 A signed
25275 RO Batt voltage grade V 12, 24, or 48

This monitor polls 25201..25274 (74 registers). The inverter returns all of them in one response when asked.

SETTINGS blocks (split into two ranges)

10103..10104

Addr RO/RW Name Unit
10103 RW Float voltage 0.1 V
10104 RW Absorb voltage 0.1 V

20118..20132

Addr RO/RW Name Unit
20118 RW Battery stop discharging voltage 0.1 V
20119 RW Battery stop charging voltage 0.1 V
20127 RW Battery low voltage 0.1 V
20128 RW Battery high voltage 0.1 V
20132 RW Max combine charger current 0.1 A

Decoded state values

Charger workstate (15201)

Value Meaning
0 Initialization mode
1 Standby
2 Charging
3 Fault
4 Flash

MPPT state (15202)

Value Meaning
0 Stop
1 Start
2 Normal work
3 MPPT limit
4 Float

Charging state (15203)

Value Meaning
0 Stop
1 Precharge
2 CC (constant current)
3 CV (constant voltage)
4 Float
5 Current derating

Inverter workstate (25201)

Value Meaning
0 PowerOn
1 SelfTest
2 OffGrid
3 Grid-Tie
4 ByPass
5 Stop
6 GridCharging

Notes on this unit

  • Battery voltage grade is 24 V (24V battery system).
  • AC voltage grade is 120 V (120V variant, not the 230V default).
  • Confirmed against live readings: Battery voltage = 28.2 V, Inverter voltage = 115.7 V, Grid voltage = 117.0 V.