123456789101112131415161718192021222324252627282930313233343536373839404142434445464748495051525354555657585960616263646566676869707172737475767778798081828384858687888990919293949596979899100101102103104105106107108109110111112113114115116117118119120121122123124125126127128129130131132133134135136137138139140141142143144145146147148149150151152153154155156157158159160161162163164165166167168169170171172173174175176177178179180181182183184185186187188189190191192193194195196197198
  1. sheet,address,type,name,unit_or_values
  2. Inverter modbusRTU (ID == 4),20000,RO,The type of machine High,"
  3. PH/EP/PV"
  4. Inverter modbusRTU (ID == 4),20001,RO,The type of machine Low,1800/3000
  5. Inverter modbusRTU (ID == 4),20002,RW,Serial number High,
  6. Inverter modbusRTU (ID == 4),20003,RW,Serial number Low,
  7. Inverter modbusRTU (ID == 4),20004,RO,Hardware version,1.00.00
  8. Inverter modbusRTU (ID == 4),20005,RO,Software version,"1.00.00
  9. "
  10. Inverter modbusRTU (ID == 4),20006,RO,Communication Protocal Edition,1.00.00
  11. Inverter modbusRTU (ID == 4),20009,RW,Battery voltage calibration coefficient,16384
  12. Inverter modbusRTU (ID == 4),20010,RW,Inverter voltage calibration coefficient,16384
  13. Inverter modbusRTU (ID == 4),20011,RW,Grid voltage calibration coefficient,"16384
  14. "
  15. Inverter modbusRTU (ID == 4),20012,RW,Bus voltage calibration coefficient,16384
  16. Inverter modbusRTU (ID == 4),20013,RW,Control Current calibration coefficient,16384
  17. Inverter modbusRTU (ID == 4),20014,RW,Inverter Current calibration coefficient,16384
  18. Inverter modbusRTU (ID == 4),20015,RW,Grid Current calibration coefficient,16384
  19. Inverter modbusRTU (ID == 4),20016,RW,Load Current calibration coefficient,16384
  20. Inverter modbusRTU (ID == 4),20101,RW,Inverter offgrid work enable,0:OFF 1:ON
  21. Inverter modbusRTU (ID == 4),20102,RW,Inverter output voltage Set,220.0V-240.0V
  22. Inverter modbusRTU (ID == 4),20103,RW,Inverter output frequency Set,50.00Hz/60.00Hz
  23. Inverter modbusRTU (ID == 4),20104,RW,Inverter search mode enable,0:OFF 1:ON
  24. Inverter modbusRTU (ID == 4),20108,RW,Inverter discharger to grid enable,"48V: 0:OFF 1:ON
  25. 24V: Null"
  26. Inverter modbusRTU (ID == 4),20109,RW,Energy use mode,"48V:1:SBU;2:SUB;3:UTI;4:SOL (for PV;PH)
  27. 1:BAU; 3:UTI;4:BOU (for EP)
  28. 12V 24V:1:SBU;;3:UTI;4:SOL (for PV;PH)
  29. 1:BU; 3:UTI (for EP)
  30. "
  31. Inverter modbusRTU (ID == 4),20111,RW,Grid protect standard,0:VDE4105; 1:UPS ; 2:home ;3:GEN
  32. Inverter modbusRTU (ID == 4),20112,RW,SolarUse Aim,"0:LBU 1:BLU(defalut)(for PV;PH)
  33. 0:LB 1:LU(defalut) (for EP)"
  34. Inverter modbusRTU (ID == 4),20113,RW,Inverter max discharger current,"48V: 0.1A(AC)
  35. 12V 24V: Null"
  36. Inverter modbusRTU (ID == 4),20118,RW,Battery stop discharging voltage,0.1V
  37. Inverter modbusRTU (ID == 4),20119,RW,Battery stop charging voltage,0.1V
  38. Inverter modbusRTU (ID == 4),20125,RW,Grid max charger current set,0.1A(DC)
  39. Inverter modbusRTU (ID == 4),20127,RW,Battery low voltage,0.1V
  40. Inverter modbusRTU (ID == 4),20128,RW,Battery high voltage,0.1V
  41. Inverter modbusRTU (ID == 4),20132,RW,Max Combine charger current,0.1A(DC)(for PV;PH)
  42. Inverter modbusRTU (ID == 4),20142,RW,System setting,
  43. Inverter modbusRTU (ID == 4),20143,RW,Charger source priority,"0:Soalr first (for PV;PH)
  44. 2:Solar and Utility(default) (for PV;PH)
  45. 3:Only Solar (for PV;PH)
  46. 2:Utility charger enable (default) (for EP)
  47. 3:Utility charger disable (for EP)
  48. "
  49. Inverter modbusRTU (ID == 4),20144,RW,Solar power balance,"0:SBD
  50. 1:SBE"
  51. Inverter modbusRTU (ID == 4),20213,RW,Remove the accumulated data,0:No remove the accumulated data 1:Remove the accumulated data
  52. Inverter modbusRTU (ID == 4),20214,RW,Reset the parameter,0:No effect 1:Action
  53. Inverter modbusRTU (ID == 4),25201,RO,work state,0:PowerOn 1:SelfTest 2:OffGrid 3:Grid-Tie 4:ByPass 5:Stop 6:Grid charging
  54. Inverter modbusRTU (ID == 4),25202,RO,AC voltage grade,"230:230V
  55. 120:120V"
  56. Inverter modbusRTU (ID == 4),25203,RO,Rated power(VA),VA
  57. Inverter modbusRTU (ID == 4),25204,RO,reserved,
  58. Inverter modbusRTU (ID == 4),25205,RO,Battery voltage,0.1V
  59. Inverter modbusRTU (ID == 4),25206,RO,Inverter voltage,0.1V
  60. Inverter modbusRTU (ID == 4),25207,RO,Grid voltage,0.1V
  61. Inverter modbusRTU (ID == 4),25208,RO,BUS voltage,0.1V
  62. Inverter modbusRTU (ID == 4),25209,RO,Control current,0.1A
  63. Inverter modbusRTU (ID == 4),25210,RO,Inverter current,0.1A
  64. Inverter modbusRTU (ID == 4),25211,RO,Grid current,0.1A
  65. Inverter modbusRTU (ID == 4),25212,RO,Load current,0.1A
  66. Inverter modbusRTU (ID == 4),25213,RO,PInverter,1W
  67. Inverter modbusRTU (ID == 4),25214,RO,PGrid,1W
  68. Inverter modbusRTU (ID == 4),25215,RO,PLoad,1W
  69. Inverter modbusRTU (ID == 4),25216,RO,Load percent,0.01
  70. Inverter modbusRTU (ID == 4),25217,RO,SInverter,1VA
  71. Inverter modbusRTU (ID == 4),25218,RO,SGrid,1VA
  72. Inverter modbusRTU (ID == 4),25219,RO,Sload,1VA
  73. Inverter modbusRTU (ID == 4),25220,RO,reserved,
  74. Inverter modbusRTU (ID == 4),25221,RO,Qinverter,1var
  75. Inverter modbusRTU (ID == 4),25222,RO,Qgrid,1var
  76. Inverter modbusRTU (ID == 4),25223,RO,Qload,1var
  77. Inverter modbusRTU (ID == 4),25224,RO,reserved,
  78. Inverter modbusRTU (ID == 4),25225,RO,Inverter frequency,0.01Hz
  79. Inverter modbusRTU (ID == 4),25226,RO,Grid frequency,0.01Hz
  80. Inverter modbusRTU (ID == 4),25227,RO,reserved,
  81. Inverter modbusRTU (ID == 4),25228,RO,reserved,
  82. Inverter modbusRTU (ID == 4),25229,RO,Inverter max number,
  83. Inverter modbusRTU (ID == 4),25230,RO,Combine type,
  84. Inverter modbusRTU (ID == 4),25231,RO,Inverter number,
  85. Inverter modbusRTU (ID == 4),25232,RO,reserved,
  86. Inverter modbusRTU (ID == 4),25233,RO,AC radiator temperature,1℃
  87. Inverter modbusRTU (ID == 4),25234,RO,Transformer temperature,1℃
  88. Inverter modbusRTU (ID == 4),25235,RO,DC radiator temperature,1℃
  89. Inverter modbusRTU (ID == 4),25236,RO,reserved,
  90. Inverter modbusRTU (ID == 4),25237,RO,Inverter relay state,0: Disconnect 1:Connect
  91. Inverter modbusRTU (ID == 4),25238,RO,Grid relay state,0: Disconnect 1:Connect
  92. Inverter modbusRTU (ID == 4),25239,RO,Load relay state,0: Disconnect 1:Connect
  93. Inverter modbusRTU (ID == 4),25240,RO,N_Line relay state,0: Disconnect 1:Connect
  94. Inverter modbusRTU (ID == 4),25241,RO,DC relay state,0: Disconnect 1:Connect
  95. Inverter modbusRTU (ID == 4),25242,RO,Earth relay state,0: Disconnect 1:Connect
  96. Inverter modbusRTU (ID == 4),25243,RO,reserved,
  97. Inverter modbusRTU (ID == 4),25244,RO,reserved,
  98. Inverter modbusRTU (ID == 4),25245,RO,Accumulated charger power high,1000KWH
  99. Inverter modbusRTU (ID == 4),25246,RO,Accumulated charger power low,0.1KWH
  100. Inverter modbusRTU (ID == 4),25247,RO,Accumulated discharger power high,1000KWH
  101. Inverter modbusRTU (ID == 4),25248,RO,Accumulated discharger power low,0.1KWH
  102. Inverter modbusRTU (ID == 4),25249,RO,Accumulated buy power high,1000KWH
  103. Inverter modbusRTU (ID == 4),25250,RO,Accumulated buy power low,0.1KWH
  104. Inverter modbusRTU (ID == 4),25251,RO,Accumulated sell power high,1000KWH
  105. Inverter modbusRTU (ID == 4),25252,RO,Accumulated sell power low,0.1KWH
  106. Inverter modbusRTU (ID == 4),25253,RO,Accumulated load power high,1000KWH
  107. Inverter modbusRTU (ID == 4),25254,RO,Accumulated load power low,0.1KWH
  108. Inverter modbusRTU (ID == 4),25255,RO,Accumulated self_use power high,1000KWH
  109. Inverter modbusRTU (ID == 4),25256,RO,Accumulated self_use power low,0.1KWH
  110. Inverter modbusRTU (ID == 4),25257,RO,Accumulated PV_sell power high,1000KWH
  111. Inverter modbusRTU (ID == 4),25258,RO,Accumulated PV_sell power low,0.1KWH
  112. Inverter modbusRTU (ID == 4),25259,RO,Accumulated grid_charger power high,1000KWH
  113. Inverter modbusRTU (ID == 4),25260,RO,Accumulated grid_charger power low,0.1KWH
  114. Inverter modbusRTU (ID == 4),25261,RO,Error message 1,
  115. Inverter modbusRTU (ID == 4),25262,RO,Error message 2,
  116. Inverter modbusRTU (ID == 4),25263,RO,Error message 3,
  117. Inverter modbusRTU (ID == 4),25264,RO,reserved,
  118. Inverter modbusRTU (ID == 4),25265,RO,Warning message 1,
  119. Inverter modbusRTU (ID == 4),25266,RO,Warning message 2,
  120. Inverter modbusRTU (ID == 4),25267,RO,reserved,
  121. Inverter modbusRTU (ID == 4),25268,RO,reserved,
  122. Inverter modbusRTU (ID == 4),25269,RO,Serial number High,
  123. Inverter modbusRTU (ID == 4),25270,RO,Serial number Low,
  124. Inverter modbusRTU (ID == 4),25271,RO,Hardware version,1.00.00
  125. Inverter modbusRTU (ID == 4),25272,RO,Software version,1.00.00
  126. Inverter modbusRTU (ID == 4),25273,RO,Batt power,W
  127. Inverter modbusRTU (ID == 4),25274,RO,Batt current,A
  128. Inverter modbusRTU (ID == 4),25275,RO,Batt voltage grade,"48:48V 24:24V
  129. 12:12V"
  130. Inverter modbusRTU (ID == 4),25276,,reserved,
  131. Inverter modbusRTU (ID == 4),25277,RO,Rated power(W),W
  132. Inverter modbusRTU (ID == 4),25278,RO,Communication Protocal Edition,1.00.00
  133. Inverter modbusRTU (ID == 4),25279,RO,Arrow Flag,bit
  134. PV Charger ModbusRtu (ID == 4),10001,RO,The type of machine,"
  135. PC1600"
  136. PV Charger ModbusRtu (ID == 4),10002,WR,Serial number High,
  137. PV Charger ModbusRtu (ID == 4),10003,WR,Serial number Low,
  138. PV Charger ModbusRtu (ID == 4),10004,RO,Hardware version,1.0.00
  139. PV Charger ModbusRtu (ID == 4),10005,RO,Software version,"1.0.00
  140. "
  141. PV Charger ModbusRtu (ID == 4),10006,WR,PV voltage calibration coefficient,16384
  142. PV Charger ModbusRtu (ID == 4),10007,WR,Battery voltage calibration coefficient,16384
  143. PV Charger ModbusRtu (ID == 4),10008,WR,Charger current calibration coefficient,"16384
  144. "
  145. PV Charger ModbusRtu (ID == 4),10103,WR,Float voltage,0.1V
  146. PV Charger ModbusRtu (ID == 4),10104,WR,Absorption voltage,0.1V
  147. PV Charger ModbusRtu (ID == 4),10105,WR,Battery low voltage(for PV;PH),0.1V
  148. PV Charger ModbusRtu (ID == 4),10106,WR,reserved,
  149. PV Charger ModbusRtu (ID == 4),10107,WR,Battery High voltage(for PV;PH),0.1V
  150. PV Charger ModbusRtu (ID == 4),10108,WR,PV max charger current(for PV;PH),0.1A
  151. PV Charger ModbusRtu (ID == 4),10110,WR,Battery type,"0:no choose 1:Use defined battery 2:lithium battery
  152. 3:SEALED_LEAD battery
  153. 4:AGM battery
  154. 5:GEL battery
  155. 6:FLOODED battery "
  156. PV Charger ModbusRtu (ID == 4),10111,WR,Battery AH,1AH
  157. PV Charger ModbusRtu (ID == 4),10112,WR,Remove the accumulated data,0:No remove the accumulated data 1:Remove the accumulated data
  158. PV Charger ModbusRtu (ID == 4),10118,WR,Battery equalization enable,0:Disable 1:Enable
  159. PV Charger ModbusRtu (ID == 4),10119,WR,Battery Equalization voltage,0.1V
  160. PV Charger ModbusRtu (ID == 4),10120,WR,reserved,reserved
  161. PV Charger ModbusRtu (ID == 4),10121,WR,Battery equalized time,1min
  162. PV Charger ModbusRtu (ID == 4),10122,WR,Battery Equalized timeout,1min
  163. PV Charger ModbusRtu (ID == 4),10123,WR,Equalization interval,1day
  164. PV Charger ModbusRtu (ID == 4),10124,WR,Equalization actived immediately,0:No effect 1:Action
  165. PV Charger ModbusRtu (ID == 4),15201,RO,Charger workstate,"0:Initialization mode
  166. 1:Selftest Mode
  167. 2: Work Mode
  168. 3:Stop Mode"
  169. PV Charger ModbusRtu (ID == 4),15202,RO,Mppt state,"0:Stop
  170. 1:MPPT
  171. 2: Current limiting"
  172. PV Charger ModbusRtu (ID == 4),15203,RO,charging state,"0:Stop
  173. 1:Absorb charge
  174. 2: Float charge
  175. 3:EQ charge"
  176. PV Charger ModbusRtu (ID == 4),15204,RO,reserved,
  177. PV Charger ModbusRtu (ID == 4),15205,RO,PV voltage,0.1V
  178. PV Charger ModbusRtu (ID == 4),15206,RO,Battery voltage,0.1V
  179. PV Charger ModbusRtu (ID == 4),15207,RO,Charger current,0.1A
  180. PV Charger ModbusRtu (ID == 4),15208,RO,Charger power,1W
  181. PV Charger ModbusRtu (ID == 4),15209,RO,Radiator temperature,1℃
  182. PV Charger ModbusRtu (ID == 4),15210,RO,External temperature,1℃
  183. PV Charger ModbusRtu (ID == 4),15211,RO,Battery Relay,
  184. PV Charger ModbusRtu (ID == 4),15212,RO,PV Relay,
  185. PV Charger ModbusRtu (ID == 4),15213,RO,Error message,Refer to frame Charger Error message 1
  186. PV Charger ModbusRtu (ID == 4),15214,RO,Warning message,Refer to frame Charger Warning message 1
  187. PV Charger ModbusRtu (ID == 4),15215,RO,BattVol Grade,1V
  188. PV Charger ModbusRtu (ID == 4),15216,RO,Rated Current,0.1A
  189. PV Charger ModbusRtu (ID == 4),15217,RO,Accumulated PV power high,1000KWH
  190. PV Charger ModbusRtu (ID == 4),15218,RO,Accumulated PV power low,0.1KWH
  191. PV Charger ModbusRtu (ID == 4),15219,RO,Accumulated day,1day
  192. PV Charger ModbusRtu (ID == 4),15220,RO,Accumulated hour,1hour
  193. PV Charger ModbusRtu (ID == 4),15221,RO,Accumulated minute,1minute